Abstract:This paper analyzed the generator tripping event during excitation limit and protection dynamic checking process of EX2100 excitation systems, and obtained the cause of the accident was the wrong increasing magnetic operation when over excitation limit action . Because the two sets of controller parameters inconsistent resulted in the excitation system trip. This paper gave some suggestions for excitation system dynamic checking test.
杨奇. 一起励磁系统过励限制引起的机组跳闸事件分析[J]. 电气技术, 2015, 16(9): 68-70.
Yang Qi. Analysis of Generator Tripping Caused by Excitation System Over Excitation Limit. Electrical Engineering, 2015, 16(9): 68-70.