The Simulation and Protective Measures Study by Simulation on VFTO in GIS
Liu Weiqing1, Yang Qin2, Deng Chuanhai1, Xiao Jieping1, Wang Han1
1. School of Electrical Engineering, Northeast Dianli University, Jilin, Jilin 132012; 2. School of Information Engineering, Northeast Dianli University, Jilin, Jilin 132012
Abstract:At present, with the wide application of Gas Insulated Switchgear(GIS) in power system, especially in Super Voltage and UHV systems, the damage of equipment caused by Very Fast Transient Over-voltage(VFTO) for disconnector operation get widespread attention. First, obtain the VFTO waveform and amplitude of some main node under Bus-side disconnector operation in a 550kV GIS by using the electromagnetic transient simulation software(ATP-EMTP). Furthermore, the measure to restrain the VFTO in GIS system is propsed by adding closing resistance, loading metal oxide arrester, using grounding switch to release residual charge, paralleling coupling capacitor in high voltage side of main transformer; the method provide a reference to design and product Super Voltage or UHV GIS equipment.
柳伟青, 杨琴, 邓传海, 肖阶平, 王涵. 550kV GIS中快速暂态过电压仿真及防护措施研究[J]. 电气技术, 2016, 17(2): 13-17.