Abstract:This paper gives a detailed analysis of pole 1 low valve group protection system broke DC overvoltage protection one-level action during the pole 1 double valve group open line test block process without DC line in UHVDC Chuxiong-Suidong HVDC project based on SIMATIC-TDC, the optimization scheme is presented for the inherent DC overvoltage protection action during the open line test block process of UHVDC based on SIMATIC-TDC, and through DC open line test simulation test was carried out by means of the real time digital simulation platform in UHVDC Chuxiong-Suidong HVDC project, this scheme effectively solves the DC voltage protection action during the open line test block process , the feasibility of the optimization scheme is verified, and in the upcoming DC control and protection software to be implemented in the optimization of UHVDC Chuxiong-Suidong HVDC project and Puer-Qiaoxiang HVDC project based on SIMATIC-TDC.
刘旭辉, 宋延涛, 张爱玲, 戴国安, 孙巍峰. 基于SIMATIC-TDC的特高压直流OLT优化策略[J]. 电气技术, 2017, 18(10): 96-100.
Liu Xuhui, Song Yantao, Zhang Ailing, Dai Guoan, Sun Weifeng. Optimization Strategy of UHVDC OLT based on SIMATIC-TDC. Electrical Engineering, 2017, 18(10): 96-100.