Abstract:Since high level TEV signal have been detected in various locations in a 35kV substation, we carried out PD detection, recognition and orientation experiment in the substation. First, according the UHF, ultrasonic and high frequency current probes' measurement, we judged that it's floating discharge. Then, according the orientation process, we found the location of the PD source.
郑荣生. 一起变电站异常局放信号的声电联合定位测试[J]. 电气技术, 2018, 19(4): 100-103.
Zheng Rongsheng. Sonic-electrical combined orientation study on an abnormal PD signal in a substaiton. Electrical Engineering, 2018, 19(4): 100-103.