Abstract:This paper mainly introduces the application of ultra-low frequency dielectric loss partial discharge test technology in 10kV XLPE cable. Through the ultra-low frequency dielectric loss partial discharge test of 19 old cables in Quanzhou area. According to IEEE 400.2—2013, the test data are analyzed. The results show that 6 of the 19 cables are in the state of concern or maintenance, and some of the cables are found with water branches. If these cables continue to be put into operation, there is a high probability of failure leading to power failure. Ultra low frequency dielectric loss test can effectively evaluate the insulation aging state of XLPE cable, provide guidance for distribution maintenance, and help to improve the safety and reliability of distribution network.
[1] 李伟, 吴麟琳, 张幸, 等. 交联聚乙烯电缆的老化及其诊断方法研究进展[J]. 绝缘材料, 2016, 49(11): 36-44, 50. [2] 杜伯学, 马宗乐, 霍振星, 等. 电力电缆技术的发展与研究动向[J]. 高压电器, 2010, 46(7): 100-104. [3] IEEE 400.2—2001. 有屏蔽电力电缆系统绝缘层现场试验与评价指引[S]. [4] IEEE P400.2/D9—2010. 有屏蔽电力电缆系统超低频方法现场试验指引[S]. [5] 吴朝阳. 配网XLPE电缆在线监测技术[C]//2010年全国输变电设备状态检修技术交流研讨会论文集, 厦门: 2010: 604-608. [6] 唐炬, 李伟, 杨浩, 等. 高压电缆附件局部放电超高频检测与分析[J]. 高电压技术, 2009, 35(7): 1571-1577. [7] Takashi S, Chiaki K, Ken Y, et al.Development of the DC superimposition bridge method for the measure- ment of high insulation resistance of medium voltage XLPE cables in operations[J]. Electrical Engineering in Japan, 1996, 116(5): 75-84. [8] Kuschel M, Plath R, Stepputat I, et al.Diagnostic Tech-niques for service-aged XLPE-insulated medium volt-age cables[C]//Proceeding of Jicable, 1995: 504-508. [9] 曾莼. 基于局放和介损的10kV XLPE电缆绝缘诊断研究[D]. 武汉: 华中科技大学, 2014. [10] 任志刚, 李伟, 周峰, 等. 基于超低频介损检测的电缆绝缘性能评估与影响因素分析[J]. 绝缘材料, 2018(4): 64-68. [11] Hernandez-Mejia J C, Perkel J, Harley R, et al. Corre- lation between tanδ diagnostic measurements and break- down performance at VLF for MV XLPE cables[J]. IEEE Transactions on Dielectrics and Electrical Insu- lation, 2009, 16(1): 162-170. [12] Zhao Jiankang, Ouyang Benhong, Zhao Xuetong.Review of influence of watertree on microstructure and properties of XLPE cable insulation mate-rial[J]. Insulating Materials, 2010(5): 50-56. [13] Abderrazzaq M H.Development of WaterTree structure in polyester resin[J]. IEEE Transaction on Dielectrics and Electrical Insulation, 2005, 12(4): 158-165. [14] Ross R, Megens M.Dielectric properties of water trees[C]//Proceedings of the IEEE International Con- ference on Properties and Applications of Di-electric Materials, 1, 2001: 455-458. [15] Garton A, Bamji S A. Oxidation and water tree format ion in service-aged XLPE cable insulation[J]. IEEE Transactions on Electrical Insulation, 1987, EI-22(4): 405-412. [16] Rasikawan S, Lshihara H, Shimizu N.Compari-son between watertreed and deteriorated regions[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 1994, 1(4): 597-603. [17] Suzuoki Y, Hayashi Y, Kato T, et al.Inception of electrical tree from WaterTree degradation at high temperature[C]//Proceedings of the 9th Interna-tional Conference on Properties and Applications of Die- lectric Materials, 2009: 408-411.