摘要 本文结合现场实际情况和故障录波波形对一起10kV线路两相故障导致10kV母线电压互感器避雷器爆炸的事故进行全面分析。分析表明,造成避雷器爆炸的主要原因是铁磁谐振及低频饱和电流,其中铁磁谐振造成的过电压是正常运行时的3.3倍。最后,本文提出相应的处理办法及改进措施,以减少由此造成的经济损失。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
万寿雄
关键词 避雷器两相故障电压互感器故障分析    
Abstract:In this paper, an explosion fault of 10kV bus potential transformer arrester caused by phase-to-phase fault of 10kV line is coM Prehensively analyzed based on the actual situation and the waveforms of fault record. The main factors that cause the arrester explosion are ferromagnetic resonance and low-frequency saturation current. The overvoltage caused by ferromagnetic resonance is 3.3 times that of normal voltage. At last, the corresponding treatment and improvement measures are put forward, which is used to reduce the economic loss.
Key wordsarrester    phase-to-phase fault    potential transformer    fault analysis   
收稿日期: 2021-05-24     
作者简介: 万寿雄(1991—),男,广西玉林人,本科,主要从事变电站综合自动化和微机保护方面的研究工作。