Abstract:This paper analyses End of Current Failure corresponding valve control strategy in HVDC. It is pointed out that a potential risk existed which can causes check-back signal can't be decteted by VBE and causes HVDC tripping in existing control strategy when low AC voltage cannot be detected by pole control systems under some critical conditions. Then this paper analyzes a HVDC tripping accident caused by AC system fault in order to validate this control strategy risk. In the last part of this paper, optimization of sampling circuit is proposed.
蒋智宇. 一起换相失败导致直流闭锁故障分析及其阀控策略优化研究[J]. 电气技术, 2016, 17(7): 96-100.
Jiang Zhiyu. The HVDC Faults Caused by End of Current Failure Analysis and its Valve Control Strategy Optimization Resurch. Electrical Engineering, 2016, 17(7): 96-100.