Abstract:When the single-phase permanent fault caused by current transformer below to the switch of 3/2 wiring way occurs, the exits to the circuit and the buses will be started for the purpose of protection. Thus, there will be a mismatch between the circuit protection and bus protection. This paper deeply analyzes a true case happened to a transformer substation of 500kV and contributes to be a reference to the substations installed with circuit-breaker protection equipment of NARI RCS-921A or RCS-921C.
廖立茜, 刘阳. 3/2接线方式下边开关的电流互感器单相永久性故障的解决[J]. 电气技术, 2013, 14(02): 71-73.
Liao Liqian, Liu Yang. Discussion on the Single-phase Permanent Fault Caused by Current Transformer Below to the Switch of 3/2 Wiring Way. Electrical Engineering, 2013, 14(02): 71-73.