Abstract:In view of large grounding grid grounding impedance correction test only by measuring the amplitude value of grounding current branch at previous, and then simple addition or subtraction but not to measure the phase shift. This will cause the grounding impedance correction error problem. This article researched and proposes a method, which using the satellite clock signal as the synchronous reference for the current branch vector test, and also develops an earth test system. This system can measure the current branch vector of the large grounding grids, and can be effectively used for grounding impedance correction.
林阳坡. 基于卫星时钟信号的大型接地网分流矢量测量研究[J]. 电气技术, 2020, 21(3): 117-120.