Abstract:In this paper, analyze the cause of the unit's loss of magnetic failure when the excitation system of Hohhot Pumped Storage Power Station is connected to the grid under the mode of pump. Modify the control mode of the load commutated inverter starting system and the synchronous device according to the control flow of each system before the generator connection. And the judgment condition of the excitation system operation mode is added in the monitoring system. Finally, achieve reliable generator connection of the excitation system under the pump mode.
安冬, 魏蔓. 抽水蓄能电站励磁系统水泵工况并网流程分析[J]. 电气技术, 2020, 21(11): 110-113.
An Dong, Wei Man. Generator connection process analysis of the excitation system under the mode of pump of pumped storage power station. Electrical Engineering, 2020, 21(11): 110-113.