Abstract:Plug-bushing inner and external insulation structure both effect the electrical field distribution. This paper mainly focus on external insulation of bushing. By means of classic formula we known that several factors influence the electric field strength of the plug-bushing. With the ANSYS simulation software, we built different models in different conditions. Then we simulated all this electric field, making a distinction and variation between different dielectric mediums such as epoxy resin and air. Finally, selecting a typical mould for trial-produce. Results showed that electric field of ANSYS simulation can give a guide of partial discharge analysis; test results also proved that bushing sample with increased earth-shielding-screen can improve PD in a certain degree.
[1] ZEESHAN A. Analysis of partial discharge in OIP bushing models[D]. Sweden: XR-EE-ETK, 2011: 1-22. [2] 李燕,淡淑恒,金建中. 环氧树脂的介电常数对高压复合套管电场分布的影响[C]. 中国高等学校电力系统及其自动化专业第二十六届学术年会暨中国电机工程学会电力系统专业委员会2010年年会论文集, 2010: 1-2. [3] 王文峰,张清杰,蒋立齐. 40.5kV开关柜穿墙套管电场分析及优化设计[J]. 华电技术, 2011, 33(2): 20-26. [4] 陈庆国,侯帅,池明赫,等. 换流变压器出线装置电场分布与绝缘结构优化[J]. 高电压技术, 2013, 39(12): 2859-2865. [5] 江汛,王仲奕. 复合高压套管的电场计算和分析[J]. 高电压技术, 2004, 30(3): 17-21. [6] 张文兵. JYN1-35(NW)型防凝露防污秽开关柜中环氧树脂穿墙套管的电场分析[J]. 高压电器, 1995(6): 32-35. [7] 刘其昶,绝缘结构总论(中册)[M]. 北京:机械工业出版社, 1987: 80-85. [8] SUH W B, YIM J Y, et al. Breakdown Voltage Characteristics in the SF6/N2 Gas Mixtures for DS/ES Compartment of a 245kV Gas Insulated Switchgear[C]. 2011 1st International Conference on Electric Power Equipment, Xi'an .Page(s): 366-369. [9] OBARI H T, INOUE T, et al. Development of the high voltage bushing for the ITER NBI[J]. Plasma Fusion Res. SERIES, 2010(9): 154-155. [10] 刘晓明,赵学云,温吉斌.超高压断路器出线套管电场数值计算与绝缘分析[J]. 沈阳工业大学学报, 2008(1): 30-31.