Detection Analysis and Treatment for Accidents Caused by Abnormal Sound of 500kV GIS |
Wu Di, Chen Rengang, Cui Yong, Liu Kuang |
Shandong Electric Power Maintenance Company, Ji’nan 250118 |
|
|
Abstract The safe and stable operation of the power grid are affected by GIS internal discharge, So, developing live testing and fault diagnosis of GIS equipment technology is absolutely necessary and significant. Combined with an example of abnormal sound defect for 500kV GIS, abnormal sound positioning and analysis is carried out through the use of ultrasonic testing, gas composition testing, infrared temperature and vibration testing and other means, the conclusion that vibration appeared inside of the equipment caused by the loosening of shield is verified by disintegration. Finally, the appropriate countermeasures and anti-accident measures are put forward.
|
Published: 22 December 2014
|
|
|
|
Cite this article: |
Wu Di,Chen Rengang,Cui Yong等. Detection Analysis and Treatment for Accidents Caused by Abnormal Sound of 500kV GIS[J]. Electrical Engineering, 2014, 15(11): 43-46.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2014/V15/I11/43
|
[1] 王万宝,李永宁,周迎新,等.GIS 超声波局部放电[1] 检测技术的应用分析[J]. 电气技术,2012(2): 49-52. [2] 王克挺. 气体绝缘全封闭组合电器应用于发电厂变电站的技术经济分析[J]. 电力科学与工程, 2010, 26(1): 27-29. [3] 王昌长, 李福祺, 高胜友. 电力设备的在线监测与故障诊断[M]. 北京: 清华大学出版社, 2006. [4] 金立军, 张明锐, 刘卫东. GIS局部放电故障诊断试验研究[J]. 电工技术学报, 2005(11). [5] 刘君华, 姚明, 黄成军, 等. 采用声电联合法的GIS局部放电定位试验研究[J]. 高电压技术, 2009, 35(10): 2458-2463. [6] 荆锴, 冯新岩, 张晓翠. 带电检测在500kV电网状态检修中的应用[J]. 山东电力技术,2013(5): 26-28, 36. [7] 刘洪正. 高压组合电器[M]. 北京: 中国电力出版社, 2013. |
|
|
|