Abstract  With the widely application of Merging Unit in the smart substation, the Digital Sample Value technique becomes an important part of the substation relay protection and control system. Assuming the grid frequency is fixed at 50Hz, the Merging Unit samples the power system with equal interval sampling technology at 80 samples per circle. When the frequency of the power grid changes, the Fourier algorithm will introduce the frequency leakage and the accuracy of both value and phase will greatly decline. To overcome this problem, the three phase soft phase-locked loop is adopted in portable IEC 61850 test equipment. Combining the three phase soft phase-locked loop and the re-sample technology, the portable IEC 61850 test equipment can still achieve high measurement accuracy when the system frequency is variable. The simulation confirms the conclusion.
Key wordsIEC 61850      three-phase soft phase-locked loop(SPLL)      re-sample      variable frequency     
Published: 28 October 2015
Service
E-mail this article
Add to my bookshelf
Add to citation manager
E-mail Alert
RSS
Articles by authors
Wu Zhenjie
Fu Guanghui
Wu Jing
Tao Tao
Cite this article:   
Wu Zhenjie,Fu Guanghui,Wu Jing等. The Application of Three Phase Soft Phase-Locked Loop in Portable IEC 61850 Test Equipment[J]. Electrical Engineering, 2015, 16(10): 84-87.
URL:  
https://dqjs.cesmedia.cn/EN/Y2015/V16/I10/84
Copyright © Electrical Engineering
Supported by: Beijing Magtech