Study of Insulation Detection of DC System for Substation |
Zhang Xun1, Li Gang2 |
1. State Grid Henan Electric Corporation Maintenance Company, Zhengzhou 450000; 2. State Grid Qinghai Electric Corporation Guinan Power Supply Company, Guinan, Qinghai 813100 |
|
|
Abstract In order to improve the reliability of the DC system in substation, the insulation of DC bus and branches should be monitored real-timely. The principle of insulation detection both based unbalanced and balanced bridge was analyzed, and the deficiency was pointed out. The voltage of positive & negative buses and the leak current of branches before and after the detection resistance put into the system were used to detect the insulation resistance. The resistances of all branches were detected and measured even if both the positive and negative of multi-branches were grounding at the same time.
|
Published: 26 October 2016
|
|
|
|
[1] 尹星光, 何铭宁, 徐玉凤, 等. 直流接地巡检装置误、漏选线问题分析[J]. 继电器, 2008, 36(10): 83-85. [2] 王友仁, 崔江, 刘新峰. 直流系统在线绝缘检测技术研究[J]. 仪器仪表学报, 2005, 26(8): 849-852. [3] 王瑞祥, 刘峰, 熊小伏, 等. 变电站直流电源绝缘在线监测新方法[J]. 电力自动化设备, 2009, 29(12): 65-67, 93. [4] 黄海宏, 陈伟, 王海欣. 多直流支路接地检测方法的研究[J]. 电子测量与仪器学报, 2011, 25(9): 793-798. [5] 黄海宏, 全成, 黄锦. 基于差流检测法的分布式直流接地巡检系统[J]. 电子测量与仪器学报, 2009, 23(11): 36-41. [6] 周军, 朱博楠, 杨圣强, 等. 基于动态差值法的直流系统绝缘监测技术[J]. 电工技术学报, 2015, 30(1): 235-241. |
|
|
|