Analysis and treatment of protection maloperation caused by secondary voltage neutral two grounding |
Xu Xingfa |
Shaoguan Power Supply Bureau, Guangdong Power Grid Corporation, Shaoguan, Guangdong 512026 |
|
|
Abstract For 110kV line zero sequence protection direction against the wrong direction of the accident. Combined with the protection device failure action waveform and the scene of the secondary wiring inspection and theoretical analysis. The cause of the cause of the malfunction is the existence of voltage transformer secondary circuit neutral point N600 two-point grounding. Put forward the relevant measures of such accidents, pointing out the necessity and importance of implementing relay protection anti-accident measures.
|
Received: 29 October 2017
Published: 21 May 2018
|
|
|
|
Cite this article: |
Xu Xingfa. Analysis and treatment of protection maloperation caused by secondary voltage neutral two grounding[J]. Electrical Engineering, 2018, 19(5): 76-79.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2018/V19/I5/76
|
[1] 饶成诚, 吴禹臻, 王海云, 等. 110kV线路零序电流方向保护校验及事故分析[J]. 电力学报, 2015(6): 466-470. [2] 罗劲松. 两起110kV线路零序方向保护反方向误动原因分析[J]. 水电能源科学, 2012, 30(4): 185-187. [3] 杨玉良, 马延涛. 一起110kV线路零序方向保护反方向误动原因分析[J]. 陕西电力, 2010(4): 49-50. [4] 南京南瑞继保电气有限公司. RCS-941A(B.D)高压输电线路成套保护装置说明书[Z]. 2007. [5] 杜兴伟, 吴征, 李娜, 等. 一起电压互感器二次回路多点接地事故分析及检查方法的研究[J]. 供用电, 2015(7): 74-76. [6] 张强, 吴绍武, 王德全. 一起线路故障引起主变中性点间隙击穿的原因分析[J]. 电气技术, 2016, 17(11): 153-156. [7] 胡泽文, 刘涤尘. 一起110kV末端线路单相接地故障分析[J]. 电气技术, 2016, 17(12): 93-97. [8] 郑玉平. TV二次回路异常对线路保护的影响[C]//第八届全国继电保护学术研讨会论文集, 北京: 中国电机工程学会, 2001: 464-471. [9] 程真何, 刘桂林. 110kV线路零序电流保护误动原因分析及对策[J]. 电测与仪表, 2014, 51(23): 120-122, 128. [10] 陈福锋, 魏曜, 王帆. 不受电压互感器二次回路两点接地影响的零序方向元件[J]. 电力系统自动化, 2010, 34(4): 70-74. [11] 国家电网公司办公厅. 关于印发《国家电网公司十八项电网重大反事故措施》(修订版)的通知[Z]. 北京, 2012.3.27. |
|
|
|