Analysis of step-over tripping accidents on 10kV power line in simple transformer substation |
PU Jun |
Sinopec Northwest Oilfield Company, Bayingol Mongolian Autonomous Prefecture, Xinjiang 841600 |
|
|
Abstract In this paper, several step-over tripping accidents which happened on 10kV power line in Tabei transformer substation are analyzed. The author reviews the recorder of the fault recorder, calculates the short circuit current on the basis of system impedance, analyzes the reliability and selectivity of protection fixed value; testes column breaker、current transformer and inrush current controller respectively. In the comprehensive test, when the short-circuit between phases happens, the inrush current controller loses efficacy. It is the main reason of the step-over tripping. The inrush controller cannot realize the selectivity of protection and cannot be used in transformer substation.
|
Received: 27 August 2020
|
|
|
|
Cite this article: |
PU Jun. Analysis of step-over tripping accidents on 10kV power line in simple transformer substation[J]. Electrical Engineering, 2021, 22(4): 73-77.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2021/V22/I4/73
|
[1] 高压交流断路器: GB 1984—2003[S] GB 1984—2003[S]. 北京: 中国标准出版社, 2014. [2] 继电保护和安全自动装置技术规程: GB/T 14258—2006[S] GB/T 14258—2006[S]. 北京: 中国标准出版社, 2006. [3] 电力设备预防性试验规程: DL/T 596—2005[S] DL/T 596—2005[S]. 北京: 中国标准出版社, 2005. [4] 熊虎, 于树义, 陈维新, 等. 柱上真空断路器的保护功能一二次融合试验研究[J]. 湖北电力, 2018, 42(2): 5-9, 31. [5] 郭亮, 安义, 邓才波, 等. 10kV配电线路保护配置方法研究[J]. 江西电力, 2018, 42(10): 14-19. [6] 李志全, 隋东阳, 刘玉民, 等. 客户分界开关涌流保护的定值整定及保护配合[J]. 农村电工, 2015, 23(3): 28-28, 29. [7] 闫鸿魁, 林莘, 徐建源. 10kV馈线涌流控制器的研制[J]. 高压电器, 2009, 45(4): 86-89, 93. [8] 季学军, 李哲, 姜玉磊, 等. 间断角原理微机变压器差动保护的研究与开发[J]. 江苏电机工程, 2008, 27(6): 5-7. |
|
|
|