Experimental and simulation study on installation and configuration mode of 10kV transmission line piercing arrester |
LIANG Kaiwang, FENG Shan |
Zhaotong Power Supply Company of Yunnan Power Grid Co., Ltd, Zhaotong, Yunnan 657000 |
|
|
Abstract Piercing arrester is the most used type of lightning arrester for 10kV overhead lines. Its installation location and installation density directly affect the lightning protection effect of the line. Therefore, this paper studies the optimal installation and configuration of the piercing arrester through experiments and simulation. Combined with P—15 pin type and PS—20 post type two typical 10kV line insulators, lightning impulse discharge experiment is carried out to study the effect of installation position on discharge path. Based on ATP-EMTP software, the calculation model of induced lightning overvoltage is established, and the variation of lightning withstand level under different installation densities of lightning arresters is analyzed. The results show that the distance between the central axis of the piercing electrode and the central axis of the insulator should not be less than 300 mm, and the air gap in series outside the arrester should be adjusted to 120 mm. It is suggested that the insulator should be replaced with PS—20 post insulator while installing arrester, and the installation density should be separate one base pole. The actual line operation verifies the simulation conclusion. According to the above principles, the actual lightning trip rate of the reconstructed line decreases by about 75%.
|
Received: 14 December 2021
|
|
|
|
Cite this article: |
LIANG Kaiwang,FENG Shan. Experimental and simulation study on installation and configuration mode of 10kV transmission line piercing arrester[J]. Electrical Engineering, 2022, 23(4): 102-108.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2022/V23/I4/102
|
[1] 薛蓉, 付慧, 马勇, 等. 配网线路防雷措施分析与研究[J]. 高压电器, 2017, 53(9): 17-22. [2] 万寿雄. 10kV不接地系统两相故障导致电压互感器避雷器爆炸事故分析[J]. 电气技术, 2021, 22(11): 56-62. [3] 傅景伟, 李小平, 姚尧, 等. 10kV架空配电线路常用防雷措施防雷性能对比研究[J]. 水电能源科学, 2019, 37(12): 132-135. [4] 朱秀兰, 李梦达. 10kV配电线路防雷保护间隙的设计[J]. 科学技术与工程, 2010, 31(10): 7755-7759. [5] 夏欣, 淡淑恒, 李翔宇, 等. 10kV防雷绝缘子引弧板参数对绝缘子电场与电位分布的影响[J]. 电瓷避雷器, 2020(2): 189-195. [6] 沈海滨, 雷挺, 贺子鸣, 等. 10kV线路用多腔室间隙防雷装置工频续流遮断能力选择建议[J]. 电网技术, 2019, 43(4): 1480-1486. [7] 贾文彬, 司马文霞, 袁涛, 等. 半密闭灭弧腔室内电弧运动特性的三维仿真和实验[J]. 电工技术学报, 2021, 36(1): 321-329. [8] 罗佳俊, 周长江, 蔡剑碧. 基于先导传播模型的化工户外装置区排放设施接闪器保护范围研究[J]. 电气技术, 2019, 20(11): 73-76. [9] 刘素芳, 陈康, 刘思贤. 10kV串联间隙金属氧化物避雷器在配电网防雷中的优化配置[J]. 电瓷避雷器, 2020(1): 76-81. [10] 王志刚, 阮观强. 基于ATP-EMTP的配电线路避雷器防雷效果及保护范围仿真分析[J]. 电瓷避雷器, 2020(1): 66-70. [11] 周玉娟, 李凯. 架空线路雷电感应过电压的避雷器与避雷线防护比较[J]. 电瓷避雷器, 2018(6): 86-90. [12] 王羽, 文习山, 蓝磊, 等. 提高架空配电线路耐雷水平的仿真分析[J]. 高电压技术, 2011, 37(10): 2471-2476. [13] 张金波, 彭晓宇, 王磊, 等. 复杂地形下架空线雷电感应过电压特性仿真研究[J]. 高电压技术, 2019, 45(11): 3718-3713. [14] 何金良, 曾嵘. 配电线路防雷保护[M]. 北京: 清华大学出版社, 2013. [15] 边凯, 陈维江, 李成榕, 等. 架空配电线路雷电感应过电压计算研究[J]. 中国电机工程学报, 2012, 32(31): 191-199. [16] 张龙, 黄亭. 基于混合式阀片的新型过电压防护装置的仿真研究[J]. 电气技术, 2019, 20(9): 52-58. [17] IEEE guide for improving the lightning performance of electric power overhead distribution lines: IEEE Std. 1410—2010[S]. US: IEEE, 2011. |
[1] |
. [J]. Electrical Engineering, 2014, 15(04): 104-106. |
|
|
|
|