|
|
Analysis and experiment of high frequency harmonic protection scheme in Xiamen flexible HVDC transmission project |
CHEN Mingquan1,2, XIAO Shiting1, YAN Changhua1,2, SHI Qingshan1, WU Jinfu1,2 |
1. Fujian Zhongshisuo Electric Power Testing & Commission Co., Ltd, Fuzhou 350007; 2. State Grid Fujian Electric Power Research Institute, Fuzhou 350007 |
|
|
Abstract Most domestic and foreign flexible HVDC transmission projects have experienced varying degrees of high frequency oscillations after being connected to the power grid. After adopting corresponding mitigation strategies, the high frequency oscillation problem still cannot be completely solved. In this paper, combined with the new application example of high frequency harmonic protection in Xiamen flexible HVDC transmission project, the principle, criterion and other logic of the high frequency harmonic protection are explained in detail. The feasibility of the scheme is verified through simulation experiments and field test. At the same time, corresponding optimization suggestions are proposed to address the shortcomings of high frequency harmonic protection, in order to provide reference for similar projects.
|
Received: 01 September 2023
|
|
|
|
Cite this article: |
CHEN Mingquan,XIAO Shiting,YAN Changhua等. Analysis and experiment of high frequency harmonic protection scheme in Xiamen flexible HVDC transmission project[J]. Electrical Engineering, 2023, 24(10): 79-84.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2023/V24/I10/79
|
[1] 胡文旺, 唐志军, 林国栋, 等. 柔性直流输电工程系统调试技术应用、分析与改进[J]. 电力自动化设备, 2017, 37(10): 197-203, 210. [2] 邹焕雄, 李超, 胡文旺, 等. 厦门柔性直流输电工程真双极大功率试验方法研究[J]. 电气技术, 2017, 18(6): 23-26, 33. [3] 吕金都, 王致杰, 王海群, 等. 柔性直流输电技术及其应用研究[J]. 电力学报, 2015, 30(4): 293-300. [4] 李剑波, 刘黎, 苗晓君, 等. 舟山多端柔直换流站起停顺序分析研究及改进[J]. 电气技术, 2015, 16(8): 88-91, 94. [5] 陈东, 乐波, 梅念, 等. ±320kV厦门双极柔性直流输电工程系统设计[J]. 电力系统自动化, 2018, 42(14): 180-185. [6] 李超, 胡文旺, 唐志军, 等. 对称双极柔性直流输电系统功率转带控制策略[J]. 高电压技术, 2018, 44(7): 2173-2180. [7] 陈明泉, 林国栋, 晁武杰, 等. 厦门柔直工程交流故障穿越失败事件分析及改进措施[J]. 电气技术, 2023, 24(2): 71-76. [8] 王姗姗, 周孝信, 汤广福, 等. 模块化多电平电压源换流器的数学模型[J]. 中国电机工程学报, 2011, 31(24): 1-8. [9] 邹毅军, 魏明洋. 模块化多电平换流器子模块故障模拟方法[J]. 电气技术, 2022, 23(4): 96-101. [10] 茆美琴, 程德健, 袁敏, 等. 基于暂态能量流的模块化多电平高压直流电网接地优化配置[J]. 电工技术学报, 2022, 37(3): 739-749. [11] 班国邦, 牛唯, 杨文勇, 等. 基于模块化多电平换流器的直流融冰装置馈线潮流控制仿真[J]. 电气技术, 2021, 22(9): 27-33. [12] 杨诗琦, 刘开培, 秦亮, 等. MMC-HVDC高频振荡问题研究进展[J]. 高电压技术, 2021, 47(10): 3485-3496. [13] 于浩天, 吕敬, 厉璇, 等. 高频振荡抑制策略对柔性直流输电系统动态性能影响的综合评估[J]. 中国电机工程学报, 2022, 42(8): 2873-2889. [14] 苑宾, 厉璇, 尹聪琦, 等. 孤岛新能源场站接入柔性直流高频振荡机理及抑制策略[J]. 电力系统自动化, 2023, 47(4): 133-141. [15] 赵峥, 李明, 田园园, 等. 江苏如东海上风电柔直工程系统谐振分析与抑制[J]. 电力建设, 2023, 44(6): 144-152. [16] 郭贤珊, 刘斌, 梅红明, 等. 渝鄂直流背靠背联网工程交直流系统谐振分析与抑制[J]. 电力系统自动化, 2020, 44(20): 157-164. [17] 杜镇宇, 阳岳希, 季柯, 等. 张北柔直工程高频谐波振荡机理与抑制方法研究[J]. 电网技术, 2022, 46(8): 3066-3075. [18] 国网设备部关于落实柔直换流站设备可靠性提升重点措施的通知: 设备直流〔2022〕145号[Z]. 北京:国家电网有限公司, 2022. [19] 郭健生, 唐志军, 石吉银, 等. 柔性直流换流变压器保护配置方案及试验技术研究[J]. 电气应用, 2018, 37(3): 72-76, 83. [20] 陈明泉, 晁武杰, 胡文旺, 等. 基于选相跳闸和无接地点跳闸的厦门柔直工程提升方案[J]. 电气技术, 2022, 23(11): 92-98. [21] 蔡振才. 国网福建省电力有限公司电力科学研究院组编. 柔性直流输电系统调试技术[M]. 北京: 中国电力出版社, 2017. [22] 继电保护和安全自动装置技术规程: GB/T 14285—2006[S] GB/T 14285—2006[S]. 北京: 中国标准出版社, 2006. |
|
|
|