Research on Evaluation of Grounding Grid and Lightning Protection Scheme in Pangang Electric Blower Station |
Tian Zhigang1, Ren Xiaohua1, Guo Youying2, Wang Qiang1, Cai Shengzhou3 |
1. Xihua University, Chengdu 610039; 2. Pan Zhihua University, Panzhihua, Sichuan 617000; 3. Panzhihua Electric Power Bureau, Panzhihua, Sichuan 617067 |
|
|
Abstract The status of grounding device is directly related to the safe operation of power system. Testing the characteristic parameters of grounding device scientifically and directly is very important to accurately assess the situation.This paper does the field test comprehensively with a mobile impulse current generator at Pangang electric blower station,according to the defects of the grounding grid and lighting protection,studies the rectification methods based on the actual situation.Due to the evaluation of grounding grid is not enough at present,the proposed methods in this article can provide reference for the evaluation and reform of grounding grid.
|
Published: 10 October 2013
|
|
|
|
Cite this article: |
Tian Zhigang,Ren Xiaohua,Guo Youying等. Research on Evaluation of Grounding Grid and Lightning Protection Scheme in Pangang Electric Blower Station[J]. Electrical Engineering, 2013, 14(08): 20-23.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2013/V14/I08/20
|
[1] 何金良, 曾嵘. 电力系统接地技术[M]. 北京: 科学出版社, 2007. [2] 杨琳, 李建明. 冲击接地电阻测量装置的研制[J]. 电力系统自动化, 2008, 32(11): 93-96. [3] 张振军, 李建明, 付东风, 等. 冲击电流法测量变电站地网电阻[C]. 2008年中国电机工程学会年会论文集, 西安: 2008. [4] 崔宇, 李建明, 戴玉松. 基于冲击电流法测量接地电阻的装置[J]. 电力学报, 2009, 24(4): 299-302. [5] 郭强, 李建明, 田志岗, 等. 采用独立地网的变电站二次系统防雷测试分析[J]. 四川电力技术, 2012, 35(2): 49-51. |
|
|
|