Differential Protection of Motor Unit in SM2 Action Analysis and Improvement Measures |
Duan Qiang |
Shanxi Province Wanjiazhai Yellow River Diversion Project Corporation, Taiyuan 030012 |
|
|
Abstract On February 9, eight o'clock, for SM2 4# motor unit in the process of start, 6# motor unit differential protection act, 6# motor unit trip. After the test and analysis, proves that due to the connection mode is not reasonable, the three-phase sampling current neutral on both sides of protection not consistent, the outside fault lead to differential current protection beyond definite value, differential protection act,and motor unit trip.
|
Published: 10 October 2013
|
|
|
|
|
|
|