Analysis of Measuring Voltage Jump in BCU in HVDC Converter Station |
Chen Guiyou, Zhu Herong, Xiong Muwen, Liu Yonggang |
NARI-Relays Electric Co., Ltd, Nanjing 211102 |
|
|
Abstract The bay and control unit plays an irreplaceable role in the integrated automation system of the substation. The measured data of bay and control unit is data sources of the state estimation, power flow analysis and other. Therefore, it is important to ensure the stability and reliability of the measurement data. Based on the example of Measuring Voltage Jump in BCU in HVDC Converter Station, analyzes the reasons of measurement data jump. It is given that the jump is caused frequency aliasing by the theoretical analysis and the measured data. Finally, the corresponding treatment measures are given, which has a high field guidance significance.
|
Published: 09 December 2015
|
|
|
|
Cite this article: |
Chen Guiyou,Zhu Herong,Xiong Muwen等. Analysis of Measuring Voltage Jump in BCU in HVDC Converter Station[J]. Electrical Engineering, 2015, 16(12): 139-141.
|
|
|
|