Application of Electric Test in the Field of Lightning Arrester based on the Actual Phase |
Wang Zhi |
Dongguan Power Supply Bureau, Dongguan, Guangdong 523000 |
|
|
Abstract This paper introduces the new method of arrester charged test now in Dongguan Power Supply Bureau, and through the leakage current and resistive component testing, successfully found a lightning protector defects. The example is given to illustrate the new method can achieve the effect to find the defect without equipment power outage, to further validate the use of arrester charged test is feasible to replace the traditional power failure preventive test.
|
Published: 22 March 2016
|
|
|
|
Cite this article: |
Wang Zhi. Application of Electric Test in the Field of Lightning Arrester based on the Actual Phase[J]. Electrical Engineering, 2016, 17(3): 108-110.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2016/V17/I3/108
|
[1] 张伟平. 避雷器阻性电流测试新方法[J]. 电瓷避雷器, 2011(6): 112-116. [2] 宋运平. 氧化锌避雷器带电测试方法探讨[J]. 硅谷, 2011(23): 36-37, 6. [3] 严玉婷, 黄炜昭, 江健武, 等. 避雷器带电测试的原理及仪器比较和现场事故缺陷分析[J]. 电瓷避雷器, 2011(2): 57-62. [4] 李开霞, 张金波, 胡钢. 用相角差法判断金属氧化物避雷器性能优劣的研究[J]. 高压电器, 2008, 44(1): 23-25, 31. [5] 杨殿成. 金属氧化物避雷器带电测试干扰分析[J]. 高压电器, 2009, 45(5): 130-132. [6] Q/CSG114002 2011. 电力设备预防性试验规程[S]. [7] 朱焕杰, 林建辉. 金属氧化物避雷器的运行故障分析及监测方法[J]. 绝缘材料, 2008, 41(3): 56-59. |
|
|
|