The Case Analysis of an Arrester On-line Measurement with base Defect |
Huang Le, Zhang Linhai |
Meizhou Power Supply Bureau of Guangdong Power Grid Co., Ltd, Meizhou, Guangdong 514000 |
|
|
Abstract In this paper, a significant reduction of the resistive current is found in a lightning conductor on-line measurement. The season was found after analysis and test. On this basis, a measure is suggested for the first time under this condition. When defect occur on the arrester, if the base also has defect, the leak current will increase, and the measured current will remain meet the criterion. This means the experimental results are invalid. And extra experiment on the base and the body of the arrester is suggested.
|
Published: 22 January 2018
|
|
|
|
[1] 赵勇军, 任妮. 金属氧化物避雷器底座绝缘电阻试验判断标准探讨[J]. 电工技术, 2014(4): 1-2. [2] 胡伟涛, 刘海锋. 组合检测技术在避雷器状态检修中的应用[J]. 电工技术, 2013(6): 18-19. [3] 徐玉华. 电气试验[M]. 2版. 北京: 中国电力出版社, 2009. [4] 王植. 基于实际相角法的避雷器现场带电测试应用[J]. 电气技术, 2016, 17(3): 108-110. [5] 严玉婷, 黄炜昭. 避雷器带电测试的原理及仪器比较和现场事故缺陷分析[J]. 电瓷避雷器, 2011(2): 57-62. [6] 王国中, 张建敏. 220kV氧化物避雷器不拆高压引线试验的尝试[J]. 电气技术, 2013, 14(4): 69-71. [7] 韩社教, 戴栋, 马西奎. 应用有限元法计算氧化锌避雷器电位分布[J]. 中国电机工程学报, 2001, 21(12): 105-108, 114. [8] 段大鹏, 江秀臣, 孙才新. 基于正交分解的MOA泄漏电流有功分量提取算法[J]. 电工技术学报, 2008, 23(8): 56-61. [9] 袁海燕, 吴剑强. 一种改进的避雷器冲击电流试验回路参数设计方法[J]. 电工技术学报, 2011, 26(11): 210-216. |
|
|
|