The analysis of three-terminal line protection act trip caused by multiple earthing of CT |
Liu Huibin, Miao Mao |
Shanxi Province Yellow River Wanjiazhai Water Affairs Group Co., Ltd, Taiyuan 030012 |
|
|
Abstract A two-point earthing of CT secondary circuit could provide a complete circuit for a external power source.The current in this circuit depends on voltage and resistance between the two earthing points. Based on a trip event happened in Yellow River Diversion Project pump station, this article has given the back ground information, analysis and modeling, to testify the assumption of the cause of trip event. It would be a good example for field engineers to deepen their knowledge of multiple earthing.
|
Received: 25 July 2017
Published: 22 January 2018
|
|
|
|
Cite this article: |
Liu Huibin,Miao Mao. The analysis of three-terminal line protection act trip caused by multiple earthing of CT[J]. Electrical Engineering, 2018, 19(1): 114-116.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2018/V19/I1/114
|
[1] 邱涛, 王攀峰, 张克元, 等. 一起二次回路两点接地引起母线保护误动的事故分析[J]. 电力系统保护与控制, 2008, 36(24): 110-112. [2] 李瑞生, 贺要锋, 樊占峰, 等. T型输电线路三端差动保护工程应用实践[J]. 电力系统保护与控制, 2010, 38(6): 119-121, 125. [3] 尹伊. 电流二次回路两点接地引起继电保护误动分析与防范措施[J]. 通信世界, 2015(05上): 233-234. [4] 李前进, 石文国, 姚亮. 高压电网T型线路保护配置方案探讨[J]. 科技创新导报, 2009(1): 106-107. [5] 苏治, 韩广瑞, 潘向华, 等. 接地故障电流入侵差动保护导致其误动作的实例分析[J]. 电力系统保护与控制, 2014(20): 135-139. [6] 王耕. 地电位变化与电子设备的接地研究[J]. 电子产品可靠性与环境试验, 2011, 29(2): 7-12. [7] 崔亚琼. 单侧电源供电线路光纤纵联差动保护[J]. 河北水利, 2015(5): 18, 24. |
|
|
|