|
|
The grounding line selection device of compensation grid based on grounded fault model |
Chen Zhongren1, Zhu Mingjun2, Huang Jian1, He Yejun1 |
1. School of Electrical Engineering, Zhongshan Polytechnic, Zhongshan, Guangdong 528404; 2. Xinyang Electric Power Company, Xinyang, He’nan 464000; |
|
|
Abstract The electrical characteristic of compensation grid is changed because of the arc-suppression coil, which brings many difficulties to grounding line selection using the electrical characteristic. And the higher transition resistance has a great influence on result of grounding line selection. To solve the above problems, a small current grounding line selection device is developed based on grounded fault model. First, a mathematical model of grounded fault is established. Transient ground fault, high resistance grounding fault and low resistance grounding fault are identified according to the mathematical models. Line selection device should be locked up when transient grounded fault. According to the characteristics of the high resistance grounding fault, the zero sequence current active component method and its increment method are adopted. The two line selection methods are less affected by the transition resistance. On this basis, a composite grounding line selection device is constituted. Matlab simulation and low-voltage experiments verify the effectiveness of the two methods and achieve satisfactory results of line selection.
|
Received: 11 June 2018
Published: 15 January 2019
|
|
|
|
Cite this article: |
Chen Zhongren,Zhu Mingjun,Huang Jian等. The grounding line selection device of compensation grid based on grounded fault model[J]. Electrical Engineering, 2019, 20(1): 42-48.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2019/V20/I1/42
|
[1] 杨林, 郑伟, 王亮, 等. 电网调控模式下的几种典型接地故障处理[J]. 电气技术, 2014, 15(10): 117-121. [2] 李晓波, 张长彦, 王崇林. 一起消弧线圈控制装置异常动作事件分析及改进措施[J]. 电力系统保护与控制, 2011, 39(10): 121-125. [3] 刘宝稳, 李晓波. 基于失谐量的消弧线圈跟踪调谐方法[J]. 电力系统保护与控制, 2013, 41(5): 6-9. [4] 金涛, 褚福亮. 基于暂态非工频零序电流的含DG新型配电网的接地选线方法[J]. 电工技术学报, 2015, 30(17): 96-105. [5] 汤涛, 黄纯, 江亚群, 等. 基于馈线零序阻抗特性的谐振接地故障选线方法[J]. 电工技术学报, 2016, 31(20): 192-201. [6] 陈忠仁, 张波. 基于小世界网络模型的补偿电网单相接地故障识别与选线[J]. 电力系统保护与控制, 2013, 41(3): 86-90. [7] 陈忠仁, 张波, 黄健. 配电网单相接地故障的识别与智能补偿控制[J]. 电瓷避雷器, 2014(2): 66-70, 76. [8] 陈忠仁, 吴维宁, 陈家宏, 等. 补偿电网阻尼率及脱谐度问题研究[J]. 继电器, 2005, 33(4): 36-39, 44. [9] 陈博博, 屈卫锋, 杨宏宇, 等. 小电流接地系统单相接地综合电弧模型与选线方法的研究[J]. 电力系统保护与控制, 2016, 44(16): 1-7. [10] 赖平, 周想凌, 邱丹. 小电流接地系统暂态电流频率特性分析及故障选线方法研究[J]. 电力系统保护与控制, 2015, 43(4): 51-57. [11] 柳瑾, 阮玉斌, 金涛, 等. 基于模糊理论的配电网多判据融合故障选线方法研究[J]. 电气技术, 2016, 17(10): 23-30. [12] 索南加乐, 杨铖, 宋国兵, 等. 模型识别用于继电保护的理论初探[J]. 电力系统保护与控制, 2010, 38(24): 23-29. [13] 严敏敏, 陈平, 周新军, 等. 基于瞬时负序分量的小电流接地选线[J]. 广东电力, 2017, 30(3): 87-93. [14] 朱晓娟, 林圣, 张姝, 等. 基于小波能量矩的高阻接地故障检测方法[J]. 电力自动化设备, 2016, 36(12): 161-168. [15] 牟龙华. 零序电流有功分量方向接地选线保护原理[J]. 电网技术, 1999, 23(9): 60-62. [16] 薛永端, 张秋凤, 颜廷纯, 等. 综合暂态与工频信息的谐振接地系统小电流接地故障选线[J]. 电力系统自动化, 2014, 38(24): 80-85. |
|
|
|