GIS factory test data system based on network digital management |
Zhu Weiqiang, Fu Yun |
Guangdong Power Grid Huizhou Power Supply Bureau, Huizhou, Guangdong 516000 |
|
|
Abstract Mainly introduces a case of main transformer outage due to the transformer's lowering of the full insulation tube busbar defect, by analyzing protection actions,checking the equipment site once, analyzing the structure of tubular bus and counting equipment failure in the same type, know the main reason for the breakdown of the bus insulation is that the bus ends are wet, and manifested as a family defect. In order to ensure that there are no similar defects and reduce the losses caused by equipment failure, two plans of total insulation busbar transformation and operation and maintenance requirements for tubular busbar are presented.
|
Received: 29 July 2018
Published: 21 May 2019
|
|
|
|
[1] 郑云海, 吴奇宝, 何华琴, 等. 全绝缘管母线局部放电的检测与分析诊断[J]. 绝缘材料, 2010, 43(4): 63-66. [2] 关芳, 杨益民. 管型屏蔽母线的应用[J]. 中国水能及电气化, 2011(5): 59-62. [3] 王树森. 管型母线在户外配电装置中的应用[J]. 山西电力技术, 1997, 17(2): 38-40. [4] 陈玉东. 全绝缘封闭管母线在HDBT水电站中的应用[J]. 水电站机电技术, 2014, 34(2): 32-33. [5] 邱太洪, 王俊波. 局放检测技术在10kV管型母线故障检测中的应用[J]. 绝缘材料, 2015, 48(4): 69-72. [6] 刘君, 胡琳. 封闭式绝缘管母线典型缺陷研究[J]. 四川电力技术, 2016, 39(2): 59-63. [7] 陈贤熙, 李国伟. 一起变压器变低全绝缘管型母线绝缘缺陷综合分析[J]. 电网技术, 2014(11): 25-28. |
|
|
|