Discussion of incomplete phase protection configurations on the HV side circuit breaker of generator-transformer unit |
Shi Guixue |
Datang Hydropower Science & Technology Research Institute Co., Ltd, Nanning 530007 |
|
|
Abstract The damage of incomplete phase working conditions to generator and transformer is analyzed, the necessity of incomplete phase protection configuration is proposed, the current situation of incomplete phase protection configuration on the HV side circuit breaker of generator-transformer unit is introduced, the effect of relevant national standards on the current situation is analyzed, the cooperative relationship between circuit breaker failure protection and three-phase inconsistency protection is analyzed, the possibility of lacking of configuration of electrical capacity three-phase inconsistency protection leading to malfunction of failure protection is put forward, the cooperative relationship between circuit breaker anti-trip circuit and three-phase inconsistency protection is analyzed, and the possibility of lacking of configuration of electrical capacity three-phase inconsistency protection leading to failure to start anti-trip function when the circuit breaker trips locally is proposed. And finally, the improvement measures and strategies to solve the problems are put forward, especially the fixed value setting principle for action time of noumenal three-phase inconsistency protection under the different situations is analyzed and explained.
|
Received: 21 March 2019
Published: 29 September 2019
|
|
|
|
Cite this article: |
Shi Guixue. Discussion of incomplete phase protection configurations on the HV side circuit breaker of generator-transformer unit[J]. Electrical Engineering, 2019, 20(10): 99-102.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2019/V20/I10/99
|
[1] 江红军. 发电机非全相运行的危害与预防策略[J]. 电力科学与工程, 2008, 24(6): 55-59. [2] GB/T 14285—2006. 继电保护和安全自动装置技术规程[S]. [3] Q/GDW1175—2013. 变压器、高压并联电抗器和母线保护及辅助装置标准化设计规范[S]. [4] 国家电网公司运维检修部. 国家电网公司十八项电网重大反事故措施(修订版)及编制说明[Z]. 北京: 中国电力出版社, 2012. [5] Q/CSG 110033—2012. 南方电网大型发电机及发变组保护技术规范[S]. [6] Q/CSG 11102001—2012. 南方电网220kV变电站二次接线标准[S]. [7] 中国南方电网有限责任公司. 关于规范断路器本体三相不一致保护运行的通知[Z]. 2011. |
|
|
|