Simulation study on insulation fault monitoring of dry-type air-core reactor based on dielectric loss angle characteristics |
Wang Han |
China United Engineering Corporation Limited Research Institute of Electric Power Engineering Design, Hangzhou 310000 |
|
|
Abstract In power system, insulation faults often occur in air-core power reactor, and they are not easily detected in the early stage by existing methods, which leads to a long-term interturn short circuit of the reactor until it burns down.In this paper, a method to monitor insulation fault in reactor is proposed by calculating the change of loss angle δ in the state of reactor operation and short circuit. A 11kV air-core power reactor is taken as the object of the research, the thin-walled solenoid model is established to calculate the inductance of reactor under working and fault conditions, and various electrical parameters in fault conditions comparing with normal working parameters are calculated. Simulation results show that loss angle δ changes fastest among loss angle δ, equivalent impedance, resistance and other parameters, in case of insulation failure. The variation of electrical parameters will increase with the radius of short circuit turn of reactor. The closer the short-circuit turn position is to the reactor center, the more obvious the numerical change is.
|
Received: 10 April 2019
Published: 19 November 2019
|
|
|
|
Cite this article: |
Wang Han. Simulation study on insulation fault monitoring of dry-type air-core reactor based on dielectric loss angle characteristics[J]. Electrical Engineering, 2019, 20(11): 57-61.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2019/V20/I11/57
|
[1] 赵春明, 王永红, 敖明, 等. 匝间短路干式空心并联电抗器电气参数变化[J]. 变压器, 2019, 56(3): 31-36. [2] Parlevliet P P, Bersee H E, Beukers A.Measurement of (post-) curing strain development with fibre Bragg gratings[J]. Polymer Testing, 2010, 29(3): 291-301. [3] Antonucci V, Cusano A, Giordano M, et al.Cure- induced residual strain build-up in a thermoset resin[J]. Composites Part A: Applied Science and Manu- facturing, 2006, 37(4): 592-601. [4] 郭磊, 庞锴, 陈瑞, 等. 安装工艺造成干式空心电抗器异常发热分析[J]. 电力电容器与无功补偿, 2014, 35(5): 70-74. [5] 林瑞聪, 缪希仁, 郭谋发, 等. 电抗器潜伏性故障特征及其耦合量分析综述[J]. 高压电器, 2015(1): 150-155. [6] Paul J P, Leost J Y, Tesseron J M.Survey of the secondary voltage control in France: present realization and investigations[J]. IEEE Transactions on Power Systems, 1987, 2(2): 505-511. [7] 吴冬文. 35kV干式电抗器温度场分布及红外测温方法研究[J]. 变压器, 2013, 50(9): 62-65. [8] 田应富. 变电站干式电抗器故障监测方法研究[J]. 南方电网技术, 2010, 4(S1): 60-63. [9] 张洁, 谭向宇, 王科, 等. 分布式布喇格传感器系统监测温度条件对干式空心电抗器的影响[J]. 科学技术与工程, 2015(16): 160-164, 180. [10] 姜志鹏, 文习山, 王羽, 等. 特高压干式空心平波电抗器温度场耦合计算与试验[J]. 中国电机工程学报, 2015, 35(20): 5344-5350. [11] 孙志勇. 干式电抗器在线监测及火警预警系统设计[D]. 济南: 山东大学, 2016. |
|
|
|