The Cause of Unsuccessful Anti-resonance with 4TV PotentialTransformer Analysis |
Zhao Pinghao, Ai Xinfa, Ai Xiaoyu |
Pingdingshan Power supply Company, Pingdingshan, He’nan 467001 |
|
|
Abstract The principle of anti-resonance with 4TV potential transformer is introduced in thispaper. The cause of unsuccessful anti-resonance in one event is analyzed, and the result shows that theinsufficient insulation level of N point is the basic reason. The insulation level of N point couldn’t resistthe resonance overvoltage, and so short-circuit by electric arc of zero-phase TV makes theanti-resonance failed. The preventive and improving measures are presented to ensure the effect ofanti-resonance with 4TV potential transformer.
|
Received: 26 June 2014
Published: 25 July 2013
|
|
|
|
Cite this article: |
Zhao Pinghao,Ai Xinfa,Ai Xiaoyu. The Cause of Unsuccessful Anti-resonance with 4TV PotentialTransformer Analysis[J]. Electrical Engineering, 2013, 14(04): 64-66.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2013/V14/I04/64
|