Analysis on cracking failure of current-connected hoop of current transformer in a substation |
Wu Xin1, Jiang Fei2, Yan Decai1 |
1. Gansu Electric Power Research Institute Technology Center Co., Ltd, Lanzhou 730070; 2. Gansu Electric Power Research Institute, Lanzhou 730070 |
|
|
Abstract In view of the fracture failure of the hoop of the power grid iron accessories, firstly, the fracture origin is preliminarily determined by observing the micro morphology of the fracture. Secondly, the fracture failure of the hoop of the power grid is detected by non-destructive testing, chemical composition analysis, hardness test, metallographic examination and other methods. The result shows that with the increase of Zn content, its stress corrosion sensitivity increases, and at the same time, it acts on the external force in the process of running and using the hoop, the internal stress of the fracture surface increases significantly in the local scope due to the change of the external dimension, forming the stress concentration, leading to the hoop fracture under the combined action of the above comprehensive factors. Finally, combined with the failure analysis, the relevant preventive measures and suggestions are put forward.
|
Received: 11 December 2019
|
|
|
|
Cite this article: |
Wu Xin,Jiang Fei,Yan Decai. Analysis on cracking failure of current-connected hoop of current transformer in a substation[J]. Electrical Engineering, 2020, 21(6): 88-90.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2020/V21/I6/88
|
[1] GB/T1176—2013. 铸造铜及铜合金[S]. [2] NB/T 47013.5—2015. 承压设备无损检测第5部分: 渗透检测[S] [3] JB/T5108—2018. 铸造黄铜金相检验[S]. [4] 胡加瑞, 谢亿, 刘纯, 等. 主变黄铜抱夹失效分析及解决措施[J]. 湖南电力, 2015, 39(1): 39-41. [5] 顾美转. 黄铜制品开裂原因分析[J]. 热加工工艺, 2000(1): 50-51, 56. [6] 柳松青. 中温渗硼应用[J]. 热加工工艺, 2000(1): 55-56. [7] 左治江, 傅乐荣, 李尧. 调温器薄壁铜本体开裂的应力分析[J]. 机械制造, 2012, 571(3): 46-48. |
|
|
|