Logic analysis and optimization of neutral bus switch failure in ultra-high voltage direct current grid project converter station |
JIANG Jincheng, WANG Hong |
EHV Branch Company of State Grid Xinjiang Electric Power Co., Ltd, Urumqi 830000 |
|
|
Abstract Neutral bus switch failure (NBSF) logic is a typical design of the control and protection system of ultra-high voltage (UHV) DC transmission project. When the DC transmission project is in bipolar operation, if one pole fails, the neutral bus switch of the fault pole cannot be opened and acts on reclosing when the protection action performs pole isolation, so it is unable to isolate the fault point. By NBSF logic, the current can be transferred through the neutral bus grounding switch (NBGS) in the station, thus the neutral bus switch of fault pole and neutral line disconnector are opened to isolate the fault point. In this paper, the specific logic of NBSF is introduced in detail. Combined with simulation, the major hidden danger of bipolar locking caused by unipolar fault on the inverter side is deeply analyzed, the optimization and improvement scheme is put forward, and the optimized scheme is simulated and verified. It is expected to provide reference for the improvement of the logic in operation engineering and future engineering design.
|
Received: 16 May 2022
|
|
|
|
Cite this article: |
JIANG Jincheng,WANG Hong. Logic analysis and optimization of neutral bus switch failure in ultra-high voltage direct current grid project converter station[J]. Electrical Engineering, 2022, 23(11): 62-73.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2022/V23/I11/62
|
[1] 浙江大学发电教研组直流输电科研组. 直流输电[M]. 北京: 水力电力工业出版社, 1985. [2] 赵畹君. 高压直流输电工程技术[M]. 北京: 中国电力出版社, 2004. [3] 雷战斐, 史磊, 柴斌, 等. ±800kV换流站NBSF功能逻辑分析及试验方法的改进[J]. 电气技术, 2017, 18(5): 132-135. [4] 张青伟, 吴金波, 艾红杰, 等. 特高压直流输电中性母线直流电流异常后逻辑判断优化的研究[J]. 电气技术, 2021, 22(3): 94-97. [5] 代书龙, 张锐, 刘百爽. 牛从直流从西站典型故障仿真分析研究[J]. 电气技术, 2020, 21(6): 95-101. [6] 张梓莹, 梁德世, 蔡淼中, 等. 机械式高压直流真空断路器换流参数研究[J]. 电工技术学报, 2020, 35(12): 2554-2561. [7] 程显, 徐鹏飞, 葛国伟, 等. 机械式真空直流断路器弧后电流测量研究[J]. 电工技术学报, 2021, 36(16): 3516-3524. [8] 林庆标, 汪洋, 宋述波, 等. 云广直流中性母线开关及其谐振回路分析[J]. 南方电网技术, 2010, 4(2): 72-74. [9] 杨万开, 衣福全, 曾南超, 等. 特高压直流中性线母线开关重合保护误动分析[J]. 电网技术, 2016, 40(6): 1759-1765. [10] 吴贻志, 曹小拐, 毛海鹏, 等. 直流输电系统停运极中性母线开关闭合对控制保护系统的影响分析[J]. 高压电器, 2013, 49(8): 44-49. [11] 周全, 王学之, 孙嘉兴. 楚穗直流中性母线开关保护动作分析及对策研究[J]. 高压电器, 2014, 50(1): 92-96. [12] 朱韬析, 杨帆. 天广直流输电系统中性母线开关动作逻辑缺陷分析[J]. 南方电网技术, 2009, 3(2): 29-31. [13] 李俊霞, 严兵, 张爱玲, 等. 特高压直流双极区直流保护系统可靠性研究[J]. 电力系统保护与控制, 2016, 44(12): 130-136. [14] 文博, 张侃君, 夏勇军, 等. 高压直流输电系统双极中性母线差动保护改进方案研究[J]. 电力系统保护与控制, 2015, 43(10): 98-103. |
|
|
|