电气技术  2013, Vol. 14 Issue (11): 91-91    DOI:
技术与应用 |
一起110kV进线跳闸事故分析与启示
陆晓彤, 滑祥, 成善武
宝钢工程技术集团有限公司, 上海 201999
Analysis and Revelation from Trip of a 110kV Incoming Protection
Lu Xiaotong, Hua Xiang, Cheng Shanwu
Baosteel Engineering & Technology Group Co., Ltd, Shanghai 201999
全文: PDF (851 KB)   HTML (1 KB) 
输出: BibTeX | EndNote (RIS)      
摘要 针对一起变电所110kV进线跳闸事故, 结合事故处理经过、保护动作情况, 对动作原因进行分析, 付母线GPT的二次接线问题是造成跳闸事故的原因。介绍了负载不平衡时三相四线制系统中中性点电压偏移的概念和公式, 提出此次事故的相关启示。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
陆晓彤
滑祥
成善武
关键词 中性点偏移接地过电压GPT    
Abstract:This paper carefully analyzes the cause of protected trip through a obstacle of a 110kV incoming system, according to accident processing and action on the protection, and found wrong secondary wiring of B bus GPT are the cause of the accident. When three - phase and four - wire system has asymmetrical load, the concept and formula about the deviation of voltage at neutral point are given, the revelation from the accident are put forward.
Key wordsneutral shift    neutral overvoltage    GPT   
收稿日期: 2014-06-26      出版日期: 2014-01-23
作者简介: 陆晓彤(1960-), 男, 专科, 江苏南通人, 工程师, 从事企业供配电系统、雷电防护相关的技术管理工作。
引用本文:   
陆晓彤, 滑祥, 成善武. 一起110kV进线跳闸事故分析与启示[J]. 电气技术, 2013, 14(11): 91-91. Lu Xiaotong, Hua Xiang, Cheng Shanwu. Analysis and Revelation from Trip of a 110kV Incoming Protection. Electrical Engineering, 2013, 14(11): 91-91.
链接本文:  
https://dqjs.cesmedia.cn/CN/Y2013/V14/I11/91