Electrical Engineering  2022, Vol. 23 Issue (11): 99-102    DOI:
Technology & Application Current Issue| Next Issue| Archive| Adv Search |
Feasibility analysis of digital communication protection applied to 10kV power system in airport terminal
ZHONG Sumei1, YAN Shi2
1. Shenzhen Metro Operation Group Co., Ltd, Shenzhen, Guangdong 518000;
2. Shenzhen Airport (Group) Co., Ltd, Shenzhen, Guangdong 518103

Download: PDF (744 KB)   HTML (1 KB) 
Export: BibTeX | EndNote (RIS)      
Abstract  As the instantaneous protection zone of sectional over-current protection is none and time of faults clearing is long in 10kV power system of airport terminal, a over-current protection with operational logic of permitting is proposed based on improvement of sectional over-current protection, which supports fast protection for whole transmission lines by the information exchange between protections. Its speed, selectivity and reliability are analyzed by operational logic of faults, and communication scheme of IEC 61850/ general object oriented substation events (GOOSE) is suggested.
Key wordsairport terminal      10kV power system      relay protection      digital communication pro- tection      operational logic of permitting     
Received: 14 July 2022     
Service
E-mail this article
Add to my bookshelf
Add to citation manager
E-mail Alert
RSS
Articles by authors
ZHONG Sumei
YAN Shi
Cite this article:   
ZHONG Sumei,YAN Shi. Feasibility analysis of digital communication protection applied to 10kV power system in airport terminal[J]. Electrical Engineering, 2022, 23(11): 99-102.
URL:  
https://dqjs.cesmedia.cn/EN/Y2022/V23/I11/99
Copyright © Electrical Engineering
Supported by: Beijing Magtech