Under-excitation Protection Value Setting and checking Based on Admittance Measurement Principle
Wang Zhengyuan1, Wu Pengyue2, Wu Jiakun3
1. Huaneng Tianjin IGCC Company Limited, Tianjin 300452; 2. Xi’an Thermal Power Research Institute, Xi’an 710032; 3. Dongfang Electric Machinery Control Equipment Co., Ltd, Deyang, Sichuan 618000
Abstract:As the generator Under-excitation protection of criterion, Static impedance circle and asynchronous impedance circle is widely used, But there are some disadvantages. Based on Admittance Measurement Principle, establish computational formula, Simulation circle of characteristic of the admittance protection, criterion of Admittance Principle was proved is immune to fluctuations of the generator voltage, and discuss its characteristic. Finally, gave the detail of setting calculation and protection checking in IGCC power plant.