Trouble shooting and analysis of abnormal alarm signal faults of converter valve cooling system module
ZHAO Weijie1, LUO Wei2,CHEN Wen1, GAN Tao1, WANG Xiaoling1
1. Kunming Bureau of EHV Power Transmission Company China Southern Power Grid, Kunming 650000; 2. Yunnan Energy Regulatory Office of National Energy Administration, Kunming 650000
Abstract:In order to understand the abnormal alarm signal of the converter valve cooling system module out-of-tolerance, on-site processing, analysis, and simulation research on the alarm of the converter valve cooling system on this issue, and the converter valve cooling system program used in this station. The principle is tested and analyzed, and the research results show that the abnormal alarm signal of the converter valve cooling system module is caused by the DC control protection system only detecting the jump signal uploaded by the converter valve cooling system. When the communication fails, the alarm signal is restored. After the communication is restored, the DC control protection system still cannot detect the current state of the converter valve cooling system, and maintains the output of the original alarm signal. Finally, the preventive measures are given based on the accident handling process and the cause of abnormal alarm signals such as module out-of-tolerance, which provides a reference for the safe and stable operation and maintenance of the converter valve cooling of the UHV converter station in the future.
赵伟杰, 罗薇, 陈文, 甘涛, 王小岭. 换流阀冷却系统模块超差等异常报警信号故障处理及原因分析[J]. 电气技术, 2021, 22(3): 69-73.
ZHAO Weijie1, LUO Wei2,CHEN Wen1, GAN Tao1, WANG Xiaoling1. Trouble shooting and analysis of abnormal alarm signal faults of converter valve cooling system module. Electrical Engineering, 2021, 22(3): 69-73.