Abstract:According to a case of maintenance and test after the outage of a 200kV line CVT, by using principle analysis, discovery and settlement of the fault of no grounding point is made when the secondary circuit switch-disconnector is broken. It is important to check up the grounding of the secondary circuit of the CVT which is either in acceptance or outage stage for maintenance. The measures to check up the grounding of the secondary circuit of the CVT are concluded in this paper.
麻震烁, 张金祥, 骆立实, 夏岩松, 陈习文. 一起220kV线路CVT二次接地缺陷的发现及原理分析[J]. 电气技术, 2016, 17(9): 132-134.
Ma Zhenshuo, Zhang Jinxiang, Luo Lishi, Xia Yansong, Chen Xiwen. Discovery and Principle Analysis of the Grounding Fault of Secondary Circuit of A 220kV Line CVT. Electrical Engineering, 2016, 17(9): 132-134.