Abstract Internal dischargefailure of the transformer has characteristics of long latent time and weak signal, etc, and it is difficult to carry out effective detection during operation, therefore the safe operation of the transformer is threatened seriously by it. According to a fault for the excessive acetylene of the transformer oil in a 500kV substation, combined with oil chromatographic analysis, a variety of live detections include infrared temperature measurement、ultrasonic partial discharge detection are applied, and according to the infared spectrum and various modes of the discharge waveform, through expert consultation and fault pattern recognition, a conclusion is reached that imperfect earth of the magnetic shield result in the discharge to shell in the transformer. Finally, the treatment scheme and preventive measures are put forward, which have a high application value.
|
Published: 22 December 2014
|
|
|
|
Cite this article: |
Chen Rengang,Yang Ronghua,Qu Wentao等. Detection and Analysis for Accident Caused by Internal Discharge of 500kV Transformer[J]. Electrical Engineering, 2014, 15(12): 106-109.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2014/V15/I12/106
|
[1] 徐澄, 肖荣. 大型变压器内部放电故障实例诊断与分析[J]. 高压电器, 2010, 46(11): 67-73. [2] 葛为民. 变压器局部放电超声定位的现场应用[J]. 高压电器, 2005, 41(5): 351-353. [3] 黄幼茹, 费翊群, 刘华, 等. 220kV及以上变压器可靠性分析[J]. 变压器, 1997, 34(4): 3-5. [4] 胡启凡, 曹利安, 谢毓城, 等. 变压器试验技术[M].北京: 机械工业出版社, 2001. [5] 邱昌容, 王乃庆. 电工设备局部放电及其测试技术[M]. 北京: 机械工业出版社, 1994. [6] 罗勇芬, 李彦明, 刘丽春. 变压器局部放电的超声波和射频联合检测技术的现状和发展[J]. 变压器, 2003, 40(12): 28-31. [7] 唐志国, 李成榕, 常文治, 等. 变压器局部放电定位技术及新兴UHF方法的关键问题[J]. 南方电网技术, 2008, 2(1): 36-40. |
|
|
|