Analysis and Treatment Measures for Accident Caused by Internal Discharge of 220kV GIS |
Guo Lei, Zhang Haijie, Chen Rengang, Liu Kuang |
Shandong Electric Power Maintenance Company, Ji’nan 250118 |
|
|
Abstract Assembly process, operating period and frequent operation are easy to cause the internal contact of GIS bad contact, leading to overheat, discharge even explosion accident. Taking the internal discharge of 220kV GIS as an example, by means of integrated inspection and test analysis on site, it is verified that the insufficiency of operation force of mechanism, which causing uncompleted closing is the main reason for the accident. Based on site actual conditions, the paper described the outage treatment method and put forward the technological process and quality control requirement. Finally, According to the accident, the preventive measures are put forward, which improve the level of the reliable operation of the equipment.
|
Published: 13 January 2016
|
|
|
|
Cite this article: |
Guo Lei,Zhang Haijie,Chen Rengang等. Analysis and Treatment Measures for Accident Caused by Internal Discharge of 220kV GIS[J]. Electrical Engineering, 2016, 17(1): 127-130.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2016/V17/I1/127
|
[1] 王卉, 陈楷. 220kVGIS母线事故处理方法探析[J]. 中国电力教育, 2010(32): 259-260. [2] 付文光, 杨玥, 韩磊, 等. GIS内部放电缺陷的综合诊断方法与实践[J]. 电气技术, 2013(2): 44-46. [3] 吴迪, 陈仁刚, 崔勇, 等. 一起500kV GIS异响缺陷的检测分析与处理[J]. 电气技术, 2014(11): 43-46, 54. [4] 王万宝, 李永宁, 周迎新, 等. GIS超声波局部放电检测技术的应用分析[J]. 电气技术, 2012(2): 49-52. [5] 刘洪正. 高压组合电器[M]. 北京:中国电力出版社, 2013. [6] 孙茁, 薛源, 郭宏伟. 126kV GIS设备典型故障分析与处理[J]. 高压电器, 2010(11): 95-98, 102. [7] 李继胜, 赵学风, 杨景刚, 等. GIS典型缺陷局部放电测量与分析[J]. 高电压技术, 2009, 35(10): 2440- 2445. [8] 顾乐, 陈隽, 刘文浩, 等. GIS局部放电圆板型内置传感器性能影响因素的研究[J]. 高压电器, 2012, 48(2): 55-59. |
|
|
|