Voltage Sag&Swell Generator Used in High & Low Voltage Ride Through Ability Test |
Yao Xinyang1, Hu Wei2, Xu Xian2, Gu Wen3, Huang Xueliang1 |
1. School of Electrical Engineering, Southeast University, Nanjing 210096; 2. State Grid Jiangsu Electric Power Company, Nanjing 210024; 3. Jiangsu Frontier Electric Technology Co., Ltd, Nanjing 211102 |
|
|
Abstract State grid company recently released the "Technical Manual Related to High&Low Voltage Ride Through of A Class of Auxiliary Inverter in Large Steam Turbine-Generator (draft)" and put forward the requirement of high & low voltage ride through ability. But there is a lack of the testing equipment. This paper proposes a 10kW voltage sag & swell generator used in high & low voltage ride through ability test for low-voltage auxiliary inverter. Its main topology is a back-to-back three-phase PWM converter. The generator can realize balanced or unbalanced voltage sag & swell from 0 to 130%UN. Experiment shows that this device can output target voltage accurately and rapidly and meet the requirements of high&low voltage ride through ability test for low-voltage auxiliary inverter in thermal power plant.
|
Published: 13 December 2016
|
|
|
|
Cite this article: |
Yao Xinyang,Hu Wei,Xu Xian等. Voltage Sag&Swell Generator Used in High & Low Voltage Ride Through Ability Test[J]. Electrical Engineering, 2016, 17(12): 31-34.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2016/V17/I12/31
|
[1] 张彦凯, 智勇, 拜润卿, 等. 火电厂辅机变频器低电压穿越能力的研究[J]. 电气传动, 2014(11): 55-58. [2] 汤伟, 刘路登, 殷骏, 等. 火电机组辅机变频调速系统低电压穿越测试[J]. 中国电力, 2016(2): 26-30. [3] 郑忠玖. 三相电压型PWM整流器控制策略及应用研究[D]. 大连: 大连理工大学, 2011. [4] (意)Angelo Baggini, 肖湘宁, 陶顺, 等. 电能质量手册[M]. 北京: 中国电力出版社, 2010: 51-198. [5] 王晓宇, 张涛, 刘树, 等. 火电厂辅机变频器低电压穿越电源[J]. 电力自动化设备, 2015(5): 152-159. |
|
|
|