Heavy gas protection fault analysis and prevention of 220kV transformer |
Chen Xiaoyun, Zhang Weiguang |
Tangshan iron and steel Group Co., Ltd, Tangshan, Heibei 063000 |
|
|
Abstract Gas relay is the main non-power protection device of the transformer . In this paper, the tripping accident caused by heavy gas protection operation of 220kV transformer is analyzed. Some in-depth investigation and analysis of possible causes was made. The cause of the accident is considered to be the transformer oil flow quickly upward surge and impact gas relay. A short time twice at the same time start and stop 2 oil pump caused by the short circuit of the substation impact of transformer. According to the problems exposed by this accident, the corresponding preventive measures was taken. At last, Proposed the testing and maintenance recommendations for transformer.
|
Received: 03 July 2017
Published: 22 January 2018
|
|
|
|
Cite this article: |
Chen Xiaoyun,Zhang Weiguang. Heavy gas protection fault analysis and prevention of 220kV transformer[J]. Electrical Engineering, 2018, 19(1): 94-96.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2018/V19/I1/94
|
[1] DL/T 572—2010. 中华人民共和国电力行业标准电力变压器运行规程[S]. [2] 黄荣辉, 张敏, 周海廷, 等. 一起线路故障引起变压器后备保护动作的原因分析[J]. 电气技术, 2015, 16(8): 134-135. [3] 刘天明. 一次变压器工程事故的理论解读和反思[J].电气技术, 2015, 16(5): 128-130. [4] 陈伟根, 龙震泽, 谢波, 等. 不同气隙尺寸的油纸绝缘气隙放电特征及发展阶段识别[J]. 电工技术学报, 2016, 31(10): 49-58. [5] 陈家斌. 电气设备故障检测诊断方法及实例[M]. 北京: 中国水利水电出版社, 2003. [6] Q/HBW 14701—2008. 华北电网有限公司企业标准电力设备交接和预防性试验规程[S]. [7] GB/T 7252—2001. 中华人民共和国国家标准变压器油中溶解气体分析和判断导则[S]. [8] 满瑞. 一起220kV电力变压器重瓦斯误动的事故分析及处理[J]. 变压器, 2016, 53(11): 61-63. |
|
|
|