Cause and treatment of one light gas action in a 500kV reactor |
Lin Lin1, Huang Ke2, Wang Jianwei1, Cheng Zhipeng1, Zhu Mengge1 |
1. State Grid Jibei Electric Power Company, Beijing 100032; 2. State Grid Energy Conservertion Service Company, Beijing 100052 |
|
|
Abstract This article introduces a case of light gas protection action failure of a 500kV reactor and illustrates the structure of the gas relay of the fault reactor and the principle of light gas action. The analysis shows that the light gas protection action is caused by improper treatment of oil-gas separation box after maintenance and unreasonable structure of oil-gas separation box, and the matters demanding attention during the maintenance of the reactor as well as the suggestions regarding upgrading the structure of the oil-gas separation box are put forward.
|
Received: 15 November 2018
Published: 16 July 2019
|
|
|
|
[1] 曹志辉, 彭春燕. 变压器非电量问题分析[J]. 变压器, 2010, 47(8): 51-54. [2] Q/GDW1799.1—2013. 国家电网公司电力安全工作规程(变电部分)[S]. [3] 杨乐. 非电量保护动作切除故障对电抗器产生的影响[J]. 电气技术, 2013, 14(9): 82-83. [4] 陈兵, 刘吉伟. 1号主变压力释放阀动作跳闸原因及分析[J]. 山东工业技术, 2014(22): 220. [5] 曹铁山, 董德, 曾勇, 等. 一次主变瓦斯保护误动的原因及预防措施[J]. 电气技术, 2017, 18(7): 103-105. [6] 王忠毅, 严平. 主变轻瓦斯保护动作后的原因分析及处理[J]. 高电压技术, 2005, 31(5): 87-88. [7] 檀英辉, 姚文军, 李佩军, 等. 500kV变压器瓦斯保护误动分析及整改[J]. 高压电器, 2012, 48(3): 117-122. [8] 李璐, 陈正鸣, 邝石, 等. 气体继电器误动作分析及处理[J]. 高压电器, 2009, 45(6): 145-147. [9] 国家电网公司. 国家电网公司十八项电网重大反事故措施[S]. 北京: 中国电力出版社, 2007. [10] 张云峰. 变压器瓦斯保护误动原因分析及应对措施[J]. 电网技术, 2008, 32(S2): 300-302. |
|
|
|