Study of neutral shift protection for ultra high voltage direct current |
Luo Lei, Ai Hongjie |
XJ Electric Co.,Ltd,Xuchang,He’nan 461000 |
|
|
Abstract Neutral shift protection of ultra high voltage direct current transmission is an important direct current protection after charging the converter transformer and before de-blocking the direct current system. During the direct current system commissioning of Jinbei converter station and Guanggu converter station, the voltage on valve side of converter transformer is abnormal after charging the converter transformer, but the neutral shift protection is not effectively detected, which brings hidden danger for direct current system de-blocking. This paper elaborates the project application of neutral shift protection, Analyses the reasons for the failure of neutral shift protection when the voltage on valve side of converter transformer is abnormal, studies the function and setting value of neutral shift protection, the optimization strategy of neutral shift protection logic, and more reasonable protection setting value suggestions are proposed. Through the real time digital simulation test, when the valve side voltage is abnormal, the optimized strategy can effectively detect and identify, and can improve the reliability of neutral shift protection in engineering application.
|
Received: 07 May 2020
|
|
|
|
[1] 张爱玲.溪洛渡送电广东同塔双回直流输电工程控制保护策略研究[J].电力系统保护与控制,2011,39(9):72-76. [2] 赵森林,卢亚军,吕鹏飞,等.特高压直流保护动作策略优化[J].电力工程技术,2017,36(4):143-149. [3] 杨田,刘晓明,吴其,等.单向直流断路器拓扑与保护策略分析[J].电工技术学报,2020,35(增刊1):259-266. [4] 李豹,马业林,熊双成,等.±800kV特高压直流保护优化研究[J].电力系统保护与控制,2014,42(16):71-75. [5] 张阳.±800kV特高压直流输电控制保护系统分析[J].通讯世界,2017(21):243-244. [6] 张志宏.±800kV特高压直流输电控制保护系统分析[J].通信电源技术,2019,36(12):36-37. [7] 王玲,文俊,司瑞华,等.UHVDC分极分层接入方式及其运行特性[J].电工技术学报,2018,33(4):730-738. [8] 黄瑶玲,王丽丽,吴萍,等.提高直流换流站直流保护动作可靠性的措施[J].电子世界,2015(20):74-75. [9] 金能,梁宇,邢家维,等.提升配电网线路保护可靠性的远方保护及其与就地保护优化配合方案研究[J].电工技术学报,2019,34(24):5221-5233. [10] 苏继锋.配电网中性点接地方式研究[J].电力系统保护与控制,2013,41(8):141-148. [11] 周建博,李莎,李晓民.110kV变压器中性点不接地方式运行时中性点保护问题研究[J].陕西电力,2012,40(4):49-52,85. [12] 孙文,禹佳,陈伟.宜宾站换流变压器阀侧电压测量故障分析及处理[J].四川电力技术,2015,38(6):51-55. [13] 陈翔宇.由一次事故引起的对配电变压器中性点偏移及过电压的思考[J].科技展望,2015,25(10):117. [14] 周仁伟,严兵,徐留杰,等.高岭换流站换流变阀侧中性点偏移保护动作的分析研究[J].微型机与应用,2016,35(4):1-3,6. [15] 唐志军.柔性直流输电工程起动策略及时间定值整定[J].电气技术,2018,19(4):63-66. [16] 苗瑜,贾轩涛,王永胜,等.宾金、灵绍特高压直流保护三取二功能配置的应用研究[J].电气技术,2019,20(10):92-98. [17] 张波,王越.中性点不接地系统同一点两相接地短路故障分析[J].继电器,2007,35(15):59-61. [18] 王丙东,蔡蕾,董旭,等.中性点不接地系统非对称短路故障分析[J].电力系统保护与控制,2017,45(3):149-153. [19] 李斌善,付红茹,曹昌睿.青藏直流阀侧末屏电压测量及监视研究[J].科技展望,2015,25(29):95. [20] 余向东,周诚.关于继电保护装置灵敏系数两个问题的探讨[J].电气应用,2010,29(19):78-81. |
|
|
|