Analysis of maloperation caused by wrong setting of exit matrix |
LOU Lingjiao, HOU Yongchun |
Maintenance Branch of State Grid Jiangsu Electric Power Co., Ltd, Nanjing 211100 |
|
|
Abstract In this paper, an event of maloperation caused by wrong setting of exit matrix is analysed. The fault phenomenon and the analysis process are expounded. Combined with the design definition of exit matrix, the corresponding relay connection and control circuit principle, it is concluded that the main cause of this accident is the wrong setting of export matrix. Finally, corresponding improvement measures and suggestions are put forward.
|
Received: 21 May 2021
|
|
|
|
[1] 继电保护和安全自动装置技术规程: GB/T 12485—2006[S]. 北京: 中国电力出版社, 2006. [2] 国家电力调度中心. 国家电网公司继电保护培训教材[M]. 北京: 中国电力出版社, 2009. [3] 国家电力调度通信中心. 电力系统继电保护典型故障分析[M]. 北京: 中国电力出版社, 2001. [4] 薛峰. 电网继电保护事故处理和案例分析[M]. 北京:中国电力出版社, 2012. [5] 国家电力调度通信中心. 电力系统继电保护典型故障分析[M]. 北京: 中国电力出版社, 2001. [6] 李卫华, 王艳春. 主接线方式与备自投的选型及使用问题[J]. 电力科技, 2013(12): 313-314. [7] 魏煌, 洪旸锦, 黄海坤. 一起110kV备自投装置拒动行为的分析及改进[J]. 电气技术, 2011, 12(7): 63-65. [8] 蒋苏静, 蒋国顺. 110kV单母分段接线中备自投装置相关问题分析及解决措施[J]. 电工技术, 2014(9): 67-69. [9] 付文竹. 备用电源自投装置的应用研究[J]. 电气应用, 2006, 25(2): 28-30. [10] 杨剑梅, 杨雪梅, 高辉. 变压器后备保护选择性与灵敏性配合问题的分析[J]. 电气技术, 2015, 16(3): 122-124. [11] 变压器、高压并联电抗器和母线保护及辅助装置标准化设计规范: Q/GDW 1175—2013[S]. 北京: 中国电力出版社, 2013. |
|
|
|