Analysis of abnormal reclosing action of 220kV circuit breaker |
LIU Yun |
Yunnan Electric Power Technology Co., Ltd, Kunming 650217 |
|
|
Abstract The abnormal action behavior of 220kV incoming line reclosing in a 220kV substation is studied, and the causes of abnormal action are analyzed. In view of the abnormal situation of single-phase instantaneous fault of the line and the actual triple tripping and triple reclosing of the circuit breaker, under the condition of determining the correct action of the protection device, starting from the cooperation between the secondary circuit and the protection, it is confirmed that the main reasons for this abnormal action are the wrong wiring of the secondary circuit and the improper cooperation between the protection. Finally, the corresponding rectification measures are put forward for the reclosing of this kind of wiring mode.
|
Received: 11 January 2022
|
|
|
|
[1] 李志军, 林建华. 一起220kV线路重合闸失败原因分析及处理[J]. 电气技术, 2016, 17(1): 136-138. [2] 刘奎, 杜鹃, 陆金凤, 等. 基于“六统一”规范的500kV输电线路二次重合闸改进方案研究[J]. 电气技术, 2020, 21(6): 111-115. [3] 高军. 220kV输电线路自动重合闸装置应用研究[J]. 机电信息, 2010(36): 109, 111. [4] 国家电力调度通信中心. 国家电网公司继电保护培训教材[M]. 北京: 中国电力出版社, 2009. [5] 娄玲娇, 侯永春. 出口矩阵设置错误导致保护误动分析[J]. 电气技术, 2021, 22(11): 47-50. [6] 于力. 3/2接线方式下自动重合闸浅析[J]. 中国设备工程, 2018(11): 199-200. [7] CSC—121A 数字式综合重合闸及断路器辅助保护装置说明书[Z]. 北京四方继保自动化股份有限公司, 2006. [8] 马越, 朱茂森. 500kV断路器保护未正确沟通三跳分析[J]. 电气技术, 2021, 22(8): 45-47. [9] 乔彦涛, 徐兴豫, 于士谦, 等. 开关死区(失灵)保护优化方案及测试应用[J]. 电气技术, 2019, 20(1): 97-100, 105. [10] 莫建平. 110kV以上继电保护整定存在的问题及解决对策[J]. 技术与市场, 2012, 19(5): 143-144. |
|
|
|