Analysis of an explosion accident of lighting arrester |
LIU Jianyue1, ZHANG Zhidong2 |
1. Skill Training Center of Shanxi Electrical Power Company (Shanxi Electric Power Technical College), Taiyuan 030000; 2. Maintenance Company of State Grid Shanxi Electrical Power Company, Taiyuan 030032 |
|
|
Abstract The handling process of a 220kV lighting arrester explosion accident is introduced in this paper. Through the on-site disassembly and careful inspection of the arrester, referring to the equipment operation and repair and test records, the cause of the explosion is analyzed. It is confirmed that the damping of the arrester due to poor sealing is the main cause of the accident. Combined with the operation of the substation, targeted live detection is suggested to detect the damping, aging and other hidden dangers of the arrester in time, and take appropriate measures to prevent the accident from happening again.
|
Received: 20 April 2023
|
|
|
|
[1] 万寿雄. 10kV不接地系统两相故障导致电压互感器避雷器爆炸事故分析[J]. 电气技术, 2021, 22(11): 56-62. [2] 张雄清, 万方培, 杨珊. 一起35kV变压器中性点避雷器故障分析[J]. 电气技术, 2019, 20(3): 115-117. [3] 张召涛, 钟光强, 李晓斌. 一起氧化锌避雷器爆炸事故分析[J]. 高压电器, 2015, 51(8): 192-196. [4] 严玉婷, 江健武, 钟建灵, 等. 金属氧化物避雷器事故分析及测试方法的比较研究[J]. 电瓷避雷器, 2011(5): 63-69. [5] 赵强, 曹力雄. 一起特高压换流站500kV断路器击穿故障分析与处理[J]. 电气技术, 2021, 22(8): 58-61. [6] 输变电设备状态检修试验规程: Q/GDW 1168—2013[S] Q/GDW 1168—2013[S]. 北京: 中国电力出版社, 2013. [7] 带电设备红外诊断应用规范: DL/T 664—2016[S] DL/T 664—2016[S]. 北京: 中国计划出版社, 2016. [8] 黄灵资, 刘昊. 基于带电检测技术的一起35kV金属氧化物避雷器缺陷分析[J]. 电气技术, 2019, 20(1): 112-115. [9] 王前斌, 罗化龙, 沈俊轶. 玉溪新兴钢铁公司10kV电压互感器爆炸事故分析[J]. 电气技术, 2015, 16(4): 125-127. |
|
|
|