Analysis of a tripping event of two substations caused by earthing switch fault |
WAN Shouxiong |
Liuzhou Power Supply Bureau of Guangxi Power Grid Corporation, Liuzhou, Guangxi 545005 |
|
|
Abstract This paper introduces a tripping accident of two substation switches caused by earthing switch fault. Through on-site investigation and analysis of protection device message and fault recording, the reason of tripping is found out and suggestions for rectification are put forward.
|
Received: 02 January 2024
|
|
|
|
[1] 贺家李, 宋从矩. 电力系统继电保护原理[M]. 4版. 北京: 中国电力出版社, 2004. [2] 张荣海. 线路距离Ⅱ段保护拒动事件分析[J]. 电工技术, 2018(23): 76-77. [3] 顾沈卉, 王学英, 霍西锋, 等. 110kV线路故障引发的继电保护动作分析[J]. 电工技术, 2019(23): 46-47. [4] 胡泽文, 刘涤尘. 一起110kV末端线路单相接地故障分析[J]. 电气技术, 2016, 17(12): 93-97. [5] 万寿雄. 10kV不接地系统两相故障导致电压互感器避雷器爆炸事故分析[J]. 电气技术, 2021, 22(11): 56-62. [6] 刘金海. 220kV变电站的继电保护系统分析[J]. 电子技术, 2021, 50(12): 186-187. [7] 金瑞, 林湘宁, 时伯年. 基于测量阻抗轨迹的接地距离保护自适应整定方法[J]. 电力系统自动化, 2022, 46(14): 185-192. [8] 蒲军. 简易变电站的10kV线路保护越级跳闸故障分析[J]. 电气技术, 2021, 22(4): 73-77. [9] 刘耀云. 一起110kV变压器保护异常跳闸事件的原因分析及防范措施[J]. 电气技术, 2022, 23(4): 92-95. [10] 中国南方电网公司. 关于对组合电器接地刀闸实施专项反事故措施的通知[Z]. 广东, 2021. |
|
|
|