Analysis of Short Circuit Ratio Index Application in Multi-Infeed-HVDC Grid |
Cheng Xin |
Guangdong Electric Power Design Institute, China Energy Engineering Group Co., Ltd, Guangzhou 510663 |
|
|
Abstract At present, HVDC has been the important form in the wide interconnected area and Large-capacity、long-distance transmission. The most number of the HVDC infeed has been formed in Guangdong Power Grid among South China Grid. The electric distance between DC inverter stations very closely and increase a lot of potential risk. South China Power Grid is used as the testing model in the paper, the voltage supporting ability of commutation bus in the multi-HVDC-infeed Guang Dong Power Grid is studied. SCRs are studied to make out if they have relationship with the voltage supporting strength of commutation bus before and after the DC latching fault. In SCR Index, there are two factors which are capacity of short circuit and HVDC power. As the BPA has been used to emulate, line’s length and the DC power continuously are adjusted to research the effect on the voltage stability of the receiving grid by the capacity of short circuit and HVDC power. As the static voltage drop level under DC and AC failure are emulated, different HVDC lines have been retained to adjust model, the effect on the voltage stability by different numbers of HVDC has been found out.
|
Published: 20 April 2016
|
|
|
|
[1] 吴冲, 李兴源, 何朝荣. 多馈入直流交互作用因子在换相失败研究中的应用[J]. 继电器, 2007, 35(9): 26-31. [2] 金小明, 周保荣, 管霖, 等. 多馈入直流交互影响强度的评估指标[J]. 电力系统自动化, 2009, 33(15):98-102. [3] 周双喜, 姜勇, 朱凌志. 电力系统电压静态稳定性指标述评[J]. 电网技术, 2001, 25(1): 1-7. [4] 管秀鹏. 南方电网暂态电压稳定分析研究[D]. 北京:清华大学, 2004. [5] 王莉丽. 影响电力系统电压稳定性的因素分析[D]. 重庆: 重庆大学, 2004. [6] 段献忠, 何仰赞, 陈德树. 论电力系统电压稳定几种实用判据和安全指标[J]. 电力系统自动化, 1994, 18(9): 36-41. [7] 王义红, 梅生伟. 基于稳定裕度指标的暂态电压稳定分析[J]. 电工电能新技术, 2007, 26(2): 39-44. [8] Paulo Fischer de Toledo. Bernt Bergdahl, Gunnar Asplund. 多馈入HVDC交直流混合系统短路比的定义和应用[J]. 南方电网技术研究, 2005, 1(6): 19-25. [9] de TOLEDO, P BERGDAHL B, ASPLUND Gunnar. Multiple Infeed Short Circuit Ratio-Aspects Related to Multiple HVDC into One AC Network[C1]. 2005 IEEE/PES Transmission and Distribution Conference & Exhibition: Asia and Pacific, Dalian, China, 2005.08. [10] Krishayya P C S, Adapa R, Holm M, et al. IEEE guide for planning DC links terminating at AC locations having low short-circuit capacities. Part I: AC/DC system interactionphenomena[R]. France: CIGRE, 1997. [11] DAVIES J B. CIGRE WG B4. 4 l Report:Systems with Multiple DC Infeed[R]. CIGRE ELECTRA, August 2007. [12] Aik Lee Hau Denis. Andersson G. INFLUENCE OF LOAD CHARACTERISTICS ON THE POWERNOLTAGE STABILITY, part 1: BASIC EQUATIONS AND RELATIONSHIPS[J]. IEEE Transactions on Power Delivery, October, 1998, 13(4): 1347-1444. |
|
|
|