Analysis of 35kV backup power automatic switching in metro |
Yan Shi1, Zhong Sumei2 |
1. Shenzhen Airport (Group) Co., Ltd, Shenzhen, Guangdong 518103; 2. Shenzhen Metro Group Co., Ltd, Shenzhen, Guangdong 518040 |
|
|
Abstract Model, logic for action, setting calculation of backup power automatic switching of main substations and 35kV substations by characteristics of 35kV power system of metro are analyzed. Problems in practice such as cooperation between backup power automatic switching of main substations and protective relaying for grounding transformer, backup power automatic switching of 35kV substations started by differential protection for lines and protection to busbar faults set for blocking backup power automatic switching, setting of delayed accelerated protection are analyzed, and related improvements are also provided to improve reliability of power system.
|
Received: 09 May 2019
Published: 18 January 2020
|
|
|
|
[1] 严平欧. 深圳特区10kV配电网中性点接地方式的探讨[J]. 高电压技术, 1996, 22(3): 22-24. [2] 国家电力调度通信中心. 国家电网公司继电保护培训教材[M]. 北京: 中国电力出版社, 2009. [3] 闫石. Z联结接地变及其保护的分析[J]. 电工技术, 2018(19): 35-37. [4] 闫石, 钟素梅. 备自投功能在REF542plus微机保护装置中的实现[J]. 黑龙江电力, 2018, 40(6): 511-517, 564. [5] 闫石. 终端变电站的主变相间短路后备保护分析[J]. 电工技术, 2018(1): 28-29, 32. [6] 中国南方电网电力调度通信中心, 广东省电力调度中心. 地区电网继电保护整定计算[M]. 北京: 中国电力出版社, 2010. [7] 姜臻, 龙永平. 110kV备自投装置风险防控原理分析[J]. 电气技术, 2016, 17(4): 146-148. [8] 唐其筠, 宁国丽, 王志远, 等. 一起35kV备自投装置非典型故障原因分析[J]. 电气技术, 2017, 18(7): 100-102. [9] 夏侯元, 颜晓娴, 黄俭平. 区域备自投系统动作引起的过负荷研究[J]. 电气技术, 2019, 20(1): 31-35. [10] 刘健. 简单配电网——用简单办法解决配电网问题[M]. 北京: 中国电力出版社, 2017. [11] 闫石, 钟素梅. 35kV经电阻接地系统备自投的改进[J]. 电工技术, 2018(23): 110-112. [12] 成云云, 王玥婷. 地区电网继电保护实用技术[M]. 北京: 中国电力出版社, 2012. [13] 苏海霞. 变电站微机保护入门: 原理及程序逻辑[M]. 北京: 中国电力出版社, 2014. |
|
|
|