Analysis of ground flashover of a 500kV composite insulator dry switching impulse voltage withstand test |
LÜ Yu, YU Rongxing, LEI Mingdong,CHEN Chaoquan |
Dali Branch, China Southern Power Grid Extra High Voltage Company, Dali, Yunnan 671000 |
|
|
Abstract Taking a 500kV AC composite insulator ground flashover of dry switching impulse voltage withstand test of the ±800kV Xin Dong HVDC project Xin Song convertor station as the background, based on test phenomena and test results, the root cause of ground flashover of composite insulator is found by simplified test model method. When the test experiment is not installed, dry switching impulse voltage withstand of composite insulator grading ring to the ground is less than the test voltage. Explore the mechanism of the use of the test experiment on the results of the dry switching impulse voltage withstand test. It provides a good experience for future test.
|
Received: 22 July 2020
|
|
|
|
[1] 赵翮选, 赵书荣, 王联章, 等. 高海拔地区紫外辐射对硅橡胶复合绝缘子老化的影响[J]. 华北电力技术, 2009(3): 10-13. [2] 姜辉. 500kV复合绝缘子沿面电场和电压分布现场实测及提高运行可靠性研究[C]//第四届全国架空输电线路技术交流研讨会论文集, 2013: 574-578. [3] 吴光亚, 蔡炜, 肖国英, 等. 复合绝缘子的运行特性及可靠性分析[J]. 电瓷避雷器, 2004(1): 3-9. [4] Insuated bushings for alternating voltage above 1000V: IEC 60137[S]. [5] 赵畹君. 高压直流输电工程技术[M]. 2版. 北京: 中国电力出版社, 2011. [6] 詹花茂, 刘波, 颜廷利, 等. 操作冲击下空间电荷对间隙放电的影响[J]. 电工技术学报, 2014, 29(2): 212-218. [7] 常美生, 张小兰. 高电压技术[M]. 北京: 高等教育出版社, 2006. |
|
|
|