江门变电站改造方案分析
黄锦明
广东电网有限责任公司江门供电局,广东 江门 529000
Jiangmen Substation Retrofit Scheme is Studied
Huang Jinming
Guangdong Power Grid Co., Ltd., Jiangmen Power Supply Bureau, Jiangmen, Guangdong 529000
全文: PDF (535 KB)   HTML (1 KB) 
输出: BibTeX | EndNote (RIS)      
摘要 随着糯扎渡直流与阳江核电的投产,500kV江门变电站的500kV出线增加,江门站的GIS设备将无法满足系统对母线穿越功率与短路电流水平的要求。为解决这一问题,对几种可行措施的实施难度、改造效果以及对系统稳定性的影响等进行了分析。综合考虑,推荐对江门站进行原地改造,将500kV配电装置改造为HGIS设备。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
黄锦明
关键词 母线穿越功率短路电流江门站改造    
Abstract:With commissioning of Nuozhadu DC project, Yangjiang nuclear power station and increase in outgoing line of 500kV jiangmen substation, GIS equipment of jiangmen substation will not be able to match bus crossing power and short circuit current of the system. To solve the problem, this paper analyses difficulty、effect and impact on the system of several possible measures. Then, jiangmen substation reconstruction is suggested. Comparing technicality, economy of two possible scheme and calculating short circuit current,the recommendatory scheme is jiangmen substation reconstruction in original area: 500kV distribution device is modified to HGIS.
Key wordsbus crossing power    short circuit current    jiangmen substation reconstruction   